7.3.1.6 Integrating a HART device in a HART modem network
+$570RGHP1HW]
Figure 7-1 HART modem
The following describes how to integrate a HART device in a HART modem network.
Requirements
A project has been created.
The device description files (EDD) for planned or already installed field devices are available
in SIMATIC PDM.
An access point of the computer is set to the COM port to which the HART modem network
is connected.
Integrating a HART device in a HART modem network
1. Open the project in the process device network view.
2. Right-click the "Networks" object in the tree structure. In the shortcut menu that opens,
select the menu command Insert New Object > Communication network.
The "Insert Object(s) - <...>" dialog box opens.
3. Click the "Assign Device Type" button.
The "Insert Object(s) - Assign Device Type" dialog box opens. You can find additional
information in the section "Insert Object - Assign Device Type" dialog box (Page 79).
4. To set the network properties, select the inserted HART modem network in the right window
and right-click. Select the Object Properties command in the displayed shortcut menu.
5. Enter the device-specific information in the "Communication" tab of the Properties dialog
for the HART modem network.
Set the master type (primary or secondary, usually secondary):
Here, you can select the "Prefer 'Long address'" check box.
Functions
7.3 Device management
Help for SIMATIC PDM (V8.2)
84 Operating Manual, 02/2014, A5E33203676-AA