EIP-200S Ethernet/IP Adapter
2.1 Operation
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB
19
When the Adapter is reset, the outputs will be deactivated during the short period that the
reset is in progress. The unit can be reset in the following ways:
● Cycling of primary device 24 VDC power
● Using the reset capabilities in the Configuration Tool
● Sending an explicit Ethernet/IP Reset service message to instance 1 of the Identity
Object with service data of 0 or 1. If service data 1 is sent, on reset the module returns to
factory default state and any user configuration is lost.
Note
When network power is removed (or if an I/O connection times out or is lost), outp
uts will go
to their configured "substitute" value according to how this parameter is set for each I/O
module. The "default" substitute value, which will be in effect in automatic configuration
mode, will be to turn off or zero outputs. Consult the individ
ual manual for the specific I/O
module if this is a concern. To set a non
-default substitute value, user configuration MUST