EasyManuals Logo

Siemens SIMATIC TD 200 User Manual

Siemens SIMATIC TD 200
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
4-5
SIMATIC TD 200 Operator Interface
C79000-G7076-C272-01
4.2 Using the Bar Graph Character Set
This sample program illustrates the bar graph character set. Version 1.1 and higher
of the TD 200 support creating a bar graph. Select the menu command Tools >
TD 200 Wizard..., as shown in Figure 4-1, and use the TD 200 Configuration
Wizard to make the following selections:
1. Select English, select bar graph character set.
2. Disable time-of-day menu, force menu, and password protection.
3. Reserve marker byte M0 for function keys, update as fast as possible.
4. Select one 40-character message.
5. Select the parameter block starting byte at VB0, message enables at VB12,
and message information at VB20.
6. Set message text: bbbbbbbbbbbbbbbbbbbb (where b is a blank)
BAR GRAPH SAMPLE
Figure 4-4 shows the data block generated in this sample.
// BEGIN TD200_BLOCK 0
// (Comments within this block should not be edited or removed)
VB0 ’TD’ // TD 200 Identification
VB2 16#90 // Set Language to English, set Update to As fast as possible
VB3 16#01 // Set the display to 40 character mode; Up key V3.2; Down key V3.3
VB4 1 // Set the number of messages
VB5 0 // Set the Function Keys notification bits to M0.0 – M0.7
VW6 20 // Set the starting address for messages to VW20
VW8 12 // Set the starting address for message enable bits to VW12
// MESSAGE 1
// Message Enable Bit V12.7
VB20 ’ BAR GRAPH SAMPLE ’
// END TD200_BLOCK 0
Figure 4-4 Data Block of the Bar Graph Sample Program
After you finish entering the parameters in the wizard, create the program shown in
Figure 4-5, download the data block and the program to a CPU, and place the
CPU in RUN mode. Adjust potentiometer 0 to display the bar graph.
Note
This example does not produce an exact representation of the analog
potentiometer value. The partial bars are approximate.
Creatin
g
Sample Pro
g
rams

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TD 200 and is the answer not in the manual?

Siemens SIMATIC TD 200 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TD 200
CategoryRecording Equipment
LanguageEnglish

Related product manuals