Technical data
15.2 Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
335
Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units
Rated switching capacity
AC-15:
6 A / 24 V AC;
6 A / 120 V AC;
3 A / 230 V AC
DC-13:
2 A / 24 V DC;
0.55 A / 60 V DC;
0.25 A / 125 V DC
Inputs (binary)
4 inputs connected to common potential that are supplied via the device
electronics (24 V DC) for measuring process signals (e.g. local control
station, key-operated switch, limit switch, etc.), freely-assignable to
control functions.
24 V DC
Cable lengths (single)
Input characteristic
300 m
Type 1 according to EN 61131-2
Thermistor motor protection (PTC binary)
Total cold resistance
1.5 kOhm
Response value
3.4 kOhm to 3.8 kOhm
Return value
1.5 kOhm to 1.65 kOhm
Sensor short-circuit response value
< 9 ohm
Cable lengths (single), conductor cross
sections:
250 m: 2.5 mm
2
150 m: 1.5 mm
2
50 m: 0.5 mm
2
Dry-running protection for centrifugal pumps by active power monitoring (for 3UF7010-1A.00-0 basic unit)
Trip level active power
0 - 750000 W (default setting: 0)
Delay time during pump operation
0 s ... 10 s
Start-up bridging time when starting pump
0 s ... 60 s
Connection of SIMOCODE pro C / pro V basic units
Tightening torque
TORQUE: 7 lb.in to 10.3 lb.in 0.8 Nm to 1.2 Nm
Connection cross sections
- Solid 2 x0.5 mm
2
... 2.5 mm
2
; 1 x 0.5 mm
2
... 4 mm
2
2 x AWG 20 to 14 / 1 x AWG 20 to 12
- Finely stranded with end sleeve 2 x 0.5 mm
2
... 1.5 mm
2
; 1 x 0.5 mm
2
... 2.5 mm
2
2 x AWG 20 to 16 / 1 x AWG 20 to 14
- PROFIBUS cable 2 x 0.34 mm
2
AWG 22