Configuring the fieldbus
7.4 PROFIdrive profile for PROFIBUS and PROFINET
Converter with control units CU250D-2
100 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
Control and status word for the positioner
Positioning control word (POS_STW)
Table 7- 6 POS_STW and interconnection with parameters in the inverter
0 1 = Follow-up mode The inverter continuously corrects the position setpoint to
follow the position actual value.
p2655[0] =
1 1 = Set reference point The inverter accepts the reference point coordinate in its
position actual value and setpoint.
p2596 =
2 1 = Reference cam active The load is currently on the reference cam. p2612 =
Reserved --- ---
5 1 = Incremental jogging active If the jogging command is active, the inverter positions the
load by the specified traversing path in a positive or negative
p2591 =
r2092.5
0 = Jogging velocity active If the jogging command is active, the inverter positions the
load with the jog velocity in the direction of the beginning or
end of the traversing range.