Installation
4.2 Electrical Installation
Converter with control units CU250D-2
46 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
Default settings of inputs and outputs
Default settings of inputs and outputs (CU250D-2)
Default setting 26: Basic positioner via inputs and outputs;
factory settings
Default setting 27: Basic positioner via fieldbus
The fieldbus interface is not active.
PROFIdrive telegram 111
Connecting the PROFINET interface
Industrial Ethernet Cables and cable length
Listed in the table below are the recommended Ethernet cables.
Table 4- 8 Recommended PROFINET cables
Industrial Ethernet FC TP Standard Cable GP 2 x 2 100 m (328 ft) 6XV1840-2AH10
Industrial Ethernet FC TP Flexible Cable GP 2 x 2
Industrial Ethernet FC Trailing Cable GP 2 x 2 85 m (278 ft) 6XV1870–2D
Industrial Ethernet FC Trailing Cable 2 x 2
Industrial Ethernet FC Marine Cable 2 x 2
The screen of the PROFINET cable must be connected with the protective earth. The solid
copper core must not be scored when the insulation is removed from the core ends.