Configuring the fieldbus
7.2 Communication via PROFINET
Converter with control units CU250D-2
90 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
Selecting a telegram
Procedure
Proceed as follows to set a specific telegram in the inverter:
Using STARTER or an operator panel, set parameter p0922 to the appropriate value.
You have set a specific telegram in the inverter.
7.2.5
Activating diagnostics via the control
The converter provides the functionality to transmit fault and alarm messages (diagnostic
messages) to the higher-level control according to the PROFIdrive error classes.
You must select the functionality in the higher-level control (see Manuals for your inverter
(Page 371)) and activate it by booting up.