A.6 Application Examples
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
357
A.6.2
Go online with STARTER via PROFINET
A.6.2.1
Adapting the PROFINET interface
If you commission the inverter with STARTER via PROFINET, then you must correctly
address your PC and allocate STARTER the interface via which it goes online with the
inverter.
Procedure
To address the inverter, proceed as follows:
1.
Establish the bus connection.
See Section Communication via
PROFINET (Page 86))
2.
From the control panel, assign the IP
address and the subnet mask address to
your computer:
3.
Go to "Start/Settings/Control Panel".
4.
Select "Network Connections".
5.
Right-click to open the properties window
of the LAN connection.
6.
In this window, select "Internet Protocol
(TCP/IP)".
7.
Select "Properties".
8.
Set 192.168.0.100 as the IP address of
the supervisor and 255.255.255.0 as
subnet mask.
In the company network it is possible that
the IP address and the subnet mask
have different values. You can obtain
these values from your network
administrator.
9.
Open the SIMATIC Manager.
10.
Assign the TCP/IP interface to "Intel(R)
PRO/100 VE Network Connection" via
"Tools/PG/PC interface".
You have allocated your computer the IP address and the address of the subnet mask, and
defined the PC interface via which STARTER goes online with the inverter.