Configuring the fieldbus
7.4 PROFIdrive profile for PROFIBUS and PROFINET
Converter with control units CU250D-2
108 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
Status word messages
Status word messages (MELDW)
Table 7- 15 Status word for messages and interconnection with parameters in the converter
0 0 = Ramp-function generator active The motor is presently
p2082[0] = r2199.5
1 = Ramp-up/ramp-down completed Speed setpoint and actual
1 1 = Torque utilization [%] < torque threshold value 2
--- p2082[1] = r2199.11
1 = |n_act| < speed threshold value 3 (p2161)
1 = |n_act| speed threshold value 2 (p2155)
6 1 = No motor overtemperature alarm The motor temperature is
within the permissible range.
p2082[6] = r2135.14
7 1 = No alarm, thermal power unit overload The converter temperature is
within the permissible range.
p2082[7] = r2135.15
8 1 = Speed setpoint - actual value deviation within
tolerance t_on
Speed setpoint and actual
speed are within the
permissible tolerance range
p2163.
p2082[8] = r2199.4
11 1 = Controller enable The speed controller is
p2082[11] = r0899.8
12 1 = Drive ready The converter is ready to be
p2082[12] = r0899.7
The motor is switched on.