Adapt inputs and outputs
6.3 Digital outputs
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
83
Digital outputs
Changing the function of a digital output
Interconnect the digital output with a binector output of
your choice.
Binector outputs are marked with "BO" in the parameter list
of the List Manual.
Table 6- 2 Binector outputs of the inverter (selection)
Deactivating digital output
f_actual >= p1082 (f_max)
Drive ready for operation
Alarm: Motor current/torque limit
Setpoint/actual value discrepancy
f_actual ≥ setpoint (f_setpoint)
A complete list of the binector outputs is provided in the List Manual.
Changing the function of a digital output - example
tput the fault message over the digital output
1, you have to connect the DO 1 with the fault message:
You can invert the signal of the digital output using parameter p0748.
For more information, see the parameter list and the function block diagram 2241 of the List
Manual.