Corrective maintenance
10.12 Reduced acceptance test after component replacement
Converter with control units CU250D-2
296 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
10.12
Reduced acceptance test after component replacement
After a component has been replaced or the firmware updated, a reduced acceptance test of
the safety functions must be performed.
Measure
Acceptance test
Acceptance test
Documentation
Replacing the Control Unit. No.
Only check the
direction of rotation of
the motor.
Supplement inverter data
Log the new checksums
Countersignature
Replacing the Power Module. Supplement the hardware version in
the inverter data
Replace the motor with an
identical pole pair number
No change.
Replace the gearbox with an
identical ratio
Replacing safety-related
peripherals (e.g. Emergency Stop
switch).
No.
Only check the control
of the safety functions
that are influenced by
the components that
have been replaced.
No change.
Inverter firmware update. No.
Supplement firmware version in the
inverter data
Log the new checksums
Countersignature.