Setting functions
8.2 Inverter control
Converter with control units CU250D-2
116 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
Jog settings
Parameter
Description
p1058
Jogging 1 speed setpoint (factory setting 150 rpm)
p1059
Jogging 2 speed setpoint (factory setting -150 rpm)
p1082
Maximum speed (factory setting 1500 rpm)
p1110
Inhibit negative direction
=0: Negative direction of rotation is enabled =1: Negative direction of rotation is
inhibited
p1111
Inhibit positive direction
=0: Positive direction of rotation is enabled =1: Positive direction of rotation is
inhibited
p1113
Setpoint inversion
=0: Setpoint is not inverted
=1: Setpoint is inverted
p1120
Ramp-function generator ramp-up time (factory setting 10 s)
p1121
Ramp-function generator ramp-down time (factory setting 10 s)
p1055 = 722.0
Jog bit 0: Select jogging 1 via digital input 0
p1056 = 722.1
Jog bit 1: Select jogging 2 via digital input 1