Setting functions
8.7 Protection and monitoring functions
Converter with control units CU250D-2
214 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
Setting parameters for the temperature monitoring
p0335
Specify the motor cooling
0: Natural cooling - with fan on the motor shaft (factory setting)
1: Forced ventilation - with a separately driven fan
2: Liquid cooling
p0601
Motor-temperature sensor type
0: No sensor (factory setting)
1: PTC (→ p0604)
2: KTY84 (→ p0604, p0605)
Motor temperature alarm threshold (factory setting 130° C)
p0605
Motor temperature fault threshold
(factory setting 145° C)
Setting for KTY84 sensor. The parameter has no significance for a PTC sensor.
p0610
Motor overtemperature response
(factory setting: 12)
Determines the behavior as soon as the motor temperature reaches the warning
threshold p0604.
0: Alarm (A07910), no fault.
1: Alarm (A07910); the converter reduces the current limit and starts the timer.
Shutdown with fault (F07011).
2: Alarm (A07910); the converter starts the timer. Shutdown with fault (F07011).
12: As for 2, but the converter considers the last shutdown temperature to calculate
Current limit (input in A)
Additional information on the motor temperature monitoring can be found in function diagram
8016 of the List Manual.