Setting functions
8.8 Application-specific functions
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
229
Function after OFF2
The brake closing time is not taken into account after an OFF2 command:
After an OFF2, the inverter issues the signal to immediately close the motor holding brake,
independent of the motor speed.
Figure 8-43 Controlling the motor holding brake after OFF2
Commissioning a motor holding brake
DANGER
Danger to life due to falling loads
For applications such as lifting equipment, cranes or elevators, there is a danger to life if
the "Motor holding brake" function is incorrectly set.
When commissioning the "Motor holding brake" function, secure any dangerous loads,
e.g. by applying the following measures:
Lower the load down to the floor
Cordon off the hazardous area so that nobody can enter it
Precondition
The motor holding brake is connected to the inverter.