Setting functions
8.8 Application-specific functions
Converter with control units CU250D-2
236 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
p0490
1)
(factory setting 0000bin)
Using the 3rd bit of the parameter value, invert the input signals of digital input 3
p0580
1)
(factory setting 0)
Connect input of probe with a digital input.
p0581
1)
(factory setting 0)
Edge for analyzing the probe signal for measuring speed list value
0: 0/1 edge
p0582
1)
(factory setting 1)
Number of pulses per revolution
p0583
1)
(factory setting 10 s)
Maximum measurement time for the probe If there is no new pulse before the
maximum measuring time elapses, the inverter sets the actual speed value in
r0586 to zero.
The time is restarted with the next pulse.
p0585
1)
(factory setting 1)
The inverter multiplies the measured speed by the gear ratio before displaying it
r0586
1)
Result of the speed calculation
p2181
(factory setting 0)
Response for evaluating load monitoring.
A07921 for speed too high
A07922 for speed outside tolerance
F07924 for speed too high
F07925 for speed outside tolerance
p2192
Load monitoring delay time
(factory setting 10 s)
Delay time for evaluating load monitoring.
p2193 = 2
Load monitoring configuration
(factory setting: 1)
2: Speed deviation and load failure monitoring.
p3230 = 586
Load monitoring actual speed value
(factory setting 0)
Result of the speed calculation with the evaluation of the speed monitoring.
p3231
Load monitoring speed deviation
(factory setting 150 rpm)
Permissible speed deviation of load monitoring.
1)
The "Probe" subfunction calculates the speed from the pulse signal of the digital input.
For more information, see the List Manual (the parameter list and function diagram 8013).