Corrective maintenance
10.3 Replacing a Control Unit with enabled safety function
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
281
21.Switch on the inverter power supply again (power on reset).
22.Perform a
reduced
acceptance test, see the section Reduced acceptance test after
component replacement (Page 296).
You have replaced the Control Unit and transferred the safety function settings from the
operator panel to the new Control Unit.