Alarms, faults and system messages
11.6 List of alarms and faults
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
321
F08501 Setpoint timeout
• Check the PROFINET connection.
• Set the controller to RUN mode.
• If the error occurs repeatedly, check the monitoring time set (p2044).
F08502 Monitoring time, sign-of-life expired
• Check the PROFINET connection.
Send configuration data not valid
• Check the PROFINET configuration
A08511 Receive configuration data not
A08526 No cyclic connection
• Activate the controller with cyclic operation.
• Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
A08565 Consistency error for adjustable
parameters
Check the following:
• IP address, subnet mask or default gateway is not correct.
• IP address or station name used twice in the network.
• Station name contains invalid characters.
F08700 Communications error A CAN communications error has occurred. Check the following:
• Bus cable.
• Baud rate (p8622).
• Bit timing (p8623).
• Master
Start the CAN controller manually with p8608 = 1 after the cause of the
F13100 Know-how protection: Copy
protection error
The know-how protection and the copy protection for the memory card
are active. An error occurred when checking the memory card.
•
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
• Deactivate the copy protection (p7765).
F13101 Know-how protection: Copy
protection cannot be activated
Insert a valid memory card.