Technical data
12.8 Electromagnetic Compatibility
Converter with control units CU250D-2
334 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
Table 12- 7 Conducted disturbance voltage and radiated emissions
EMC Phenomenon
Converter type
Remark
Level acc. to
IEC 61800-3
Conducted emissions
(disturbance voltage)
All converters with integrated class A filters.
Order number:
6SL3525-0PE**-*A**
Category C2
First Environment -
Professional Use
Radiated emissions Converter frame sizes A, B and C with integrated
class A filter.
Order number:
6SL3525-0PE17-*
A
**
6SL3525-0PE21-*
A
**
6SL3525-0PE23-*
A
**
6SL3525-0PE24-*
A
**
6SL3525-0PE25-*
A
**
6SL3525-0PE27-*
A
**
In a domestic environment this product may cause
radio interference in which case supplementary
mitigation measures may be required.
Category C2
First Environment -
Professional Use
Harmonic Currents
Table 12- 8 Harmonic Currents
Typical Harmonic Current (% of rated input current) at U
K
1 %
5th
7th
11th
13th
17th
19th
23rd
25th
54
39
11
5
5
3
2
2
Note
Units installed within the category
C2 (domestic) environment require supply authority
acceptance for connection to the public low
-voltage power supply network. Please contact
your local supply netwo
rk provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.