Installation
4.2 Electrical Installation
Converter with control units CU250D-2
50 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
If no other restrictions apply, then select the power bus fusing according to the following
table.
Table 4- 12 Maximum fusing of the power bus
Rated power of the smallest inverter
connected to the power bus
Maximum permissible fusing
1
1
The values do not apply to installations conforming to UL specifications.
Figure 4-15 Fusing several inverters connected to a power bus
The maximum permissible fusing of 32 A is based on the inverter with the lowest rated
power of 3 kW.
If the inverters are never simultaneously in operation, then also lower cable cross-sections
are permissible and smaller fuses are required.