Commissioning
5.2 Preparing for commissioning
Converter with control units CU250D-2
Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
59
Vector control with encoder
Sensorless vector control
U/f control
With the position control, provides the best
results
Limited functionality of the position
control.
Low accuracy
Travel to fixed stop is not
possible
Not recommended in conjunction
with position control.
Low accuracy
Low dynamic response
Travel to fixed stop is not
possible
It is not permissible to use vector control in the following cases:
If the motor is too small in comparison to the inverter (the rated motor power may not be
less than one quarter of the rated inverter power)
If several motors are connected to one inverter
If a power contactor is used between the inverter and motor and is opened while the
motor is powered up
If the maximum motor speed exceeds the following values:
Inverter pulse frequency
2 kHz
4 kHz and higher
Pole number of the motor
2-pole
4-pole
6-pole
2-pole
4-pole
6-pole
Maximum motor speed [rpm]
9960
4980
3320
14400
7200
4800