Operation   
8.5 Special functions 
  Installation and Operating Instructions SINAMICS G180 
158  Operating Instructions, 02/2019, 4BS0751-007 
Table 8- 8  Line contactor functions 
External control voltage fuse protection 
-F2  Inverter output section fuse protection 
-K1  Input side main contactor 
Design recommendation: AC1 current of the contactor is at least the inverter input current 
101, 102  External control voltage for the 230 V inverter 
Digital output for the main contactor control 
Mains power connection switched via main contactor 
Main contactor feedback input 
Jumper for ground connection 
 
 
 
Coil currents in excess of 1 A at contact 41/42 
If you load the contact 41/42 with coil currents of more than 1 A, the contact can be 
destroyed. 
In the case of coil currents of more than 1 A, connect an auxiliary relay between terminal 
41/42 and the main contactor coil. 
Make the following settings in order to activate the main contactor function: 
●  The preselection for the inputs/outputs for the control must be as follows: 
–  "P-DRIVE DATA/A=Namur" or 
–  "P-DIGITAL OUTPUTS/Relay 2=MainCntctr" and "P-OPERATION/Feedb.MC=X2:8" 
●  For "P-INV. BEHAVIOUR/MCfunc" the setting "LinC…" must be input.