Operation
8.5 Special functions
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
159
Motor contactor
The inverter controls the contactor at the inverter output.
Perform the activation as for the line contactor.
Different than for the line contactor, for "P-INV. BEHAVIOUR/MCfunc" as value select the
parameters that have "MS" as prefix for motor contactor.
Dimension the output side contactor according to the AC3 current.
Perform the wiring in accordance with the following plan:
Figure 8-26 Motor contactor function