Electrical installation
4.9 Other connections
Drive converter cabinet units
112 Operating Instructions, 07/07, A5E00288214A
Terminal Designation Default value Comments
17
18
Power Disconnection EMERGENCY STOP circuit
30
31
Ready Relay output (NO contact)
32
33
Motor turning Relay output (NO contact)
34 DO (NO)
35 DO (COM)
36 DO (NC)
Fault Relay output (two-way contact)
50/51 AI 0/4-20 mA Speed setpoint Default: 4 to 20 mA
60/61 AO 0/4-20 mA Motor frequency Default: 4 to 20 mA
62/63 AO 0/4-20 mA Motor current Default: 4 to 20 mA
Max. connectable cross-section: 2.5 mm² (AWG 12)
Table 4-51 Terminal block -A1-X3 – connection for the motor PTC thermistor sensor
Terminal Designation Default value Comments
90/91 AI Connection for a PTC thermistor Shutdown if limit value is exceeded.
Max. connectable cross-section: 2.5 mm² (AWG 12)
Adapting the analog inputs and outputs
If the setting ranges of the analog inputs and outputs are to be changed, the associated
interface converters (U401 / U402 / U403) must be set. The corresponding interface
converter must be removed for this purpose and the rotary switch on the side ("S1") turned
to the corresponding position.
Table 4-52 Terminal block -A1-X2 – Adaptation of analog inputs and outputs
Terminal Designation Item code of interface converter Settings on rotary switch S1
50/51 AI U401 2: 0 - 20 mA
4: 4 - 20 mA (preassignment)
60/61 AO U402 1: 0 - 20 mA
2: 4 - 20 mA (preassignment)
62/63 AO U403 1: 0 - 20 mA
2: 4 - 20 mA (preassignment)