Functions, monitoring, and protective functions
9.2 Active Infeed functions
Drive converter cabinet units
304 Operating Instructions, 07/07, A5E00288214A
Parameters
• p3410
Infeed identification method
• r3411
Infeed identified inductance
• r3412
Infeed DC-link capacitance identified
• p3421
Infeed DC link capacitance
• p3422
Reference variable of technological unit
• p3620
Infeed current controller adaptation lower application threshold
• p3622
Infeed current controller adaptation reduction factor
9.2.2 Harmonics controller
Description
Harmonics in the supply voltage cause harmonics in the line currents. Current harmonics
can be reduced by activating the harmonics controller.
Example: setting the harmonics controller
The 5th and 7th harmonic are to be compensated:
Table 9-1 Sample parameters for the harmonics controller
Index p3624 Infeed harmonics controller
order
p3625 scaling
[0] 5 100 %
[1] 7 100 %
0% scaling means that the harmonics controller has been deactivated.
100 % scaling means that the harmonics controller has been activated with standard gain.
The phase currents in parameter p0069[0...2] (U, V, W) can be verified using the STARTER
trace function.
Parameters
• r0069[0...6]
Phase current, actual value
• p3624[0...1]
Infeed harmonics controller order
• p3625[0...1]
Infeed harmonics controller scaling