Electrical installation   
4.6 Power connections 
  Drive converter cabinet units 
54  Operating Instructions, 07/07, A5E00288214A 
 
 
Note 
If an incorrect rotating field was connected when the cables were installed, and the rotating 
field cannot be corrected by swapping the motor cables, it can be corrected when 
commissioning the drive via p1821 (rotating field direction reversal) by changing the rotating 
field and thus enabling a direction reversal (see section "Direction reversal"). 
With motors that can be operated in a star/delta configuration, the windings must be checked 
to ensure that they have been connected properly. Please refer to the relevant 
documentation for the motor and note the required insulation voltage for operating the 
cabinet unit. 
 
4.6.3  Adjusting the fan voltage (-G1 -T10, -U1 -T10) 
The power supply for the device fans (230 V 1 AC) in the Active Line Module (-G1 -T10) and 
in the Motor Module (-U1 -T10) is generated from the main supply system by means of 
transformers.  
The locations of the transformers are indicated in the layout diagrams supplied.  
The transformers are fitted with primary taps so that they can be fine-tuned to the rated 
supply voltage. When delivered, the taps are always set to the highest level. With a low 
supply voltage, the appropriate transformer tap must be activated.  
 
 
Note 
Two transformers (-G1 –T10 and -T20 or -U1 –T10 and -T20) are installed in the following 
cabinet units. The two primary terminals on these devices must be set together. 
•  With 380 V – 480 V 3 AC:  
6SL3710-7LE36-1AA0, 6SL3710-7LE37-5AA0, 6SL3710-7LE38-4AA0, 6SL3710-7LE41-
0AA0, 6SL3710-7LE41-2AA0, 6SL3710-7LE41-4AA0 
•  With 660 V – 690 V 3 AC:  
6SL3710-7LH34-1AA0, 6SL3710-7LH34-7AA0, 6SL3710-7LH35-8AA0, 6SL3710-7LH37-
4AA0, 6SL3710-7LH38-1AA0, 6SL3710-7LH38-8AA0, 6SL3710-7LH41-0AA0, 6SL3710-
7LH41-3AA0 
•  With 500 V – 600 V 3 AC:  
6SL3710-7LG34-1AA0, 6SL3710-7LG34-7AA0, 6SL3710-7LG35-8AA0, 6SL3710-
7LG37-4AA0, 6SL3710-7LG38-1AA0, 6SL3710-7LG38-8AA0, 6SL3710-7LG41-0AA0, 
6SL3710-7LG41-3AA0 
 
The setting terminals must be connected to "0" and the supply voltage.