Functions, monitoring, and protective functions
9.3 Drive functions
Drive converter cabinet units
330 Operating Instructions, 07/07, A5E00288214A
Note
The example described only applies to a SINAMICS S150 without option G61. With
option G61, steps 5 and 6 also have to be carried out for DO5 (2nd TM31).
Maximum output frequencies achieved by increasing the pulse frequency
By multiplying the basis pulse frequency (with integers), the following output frequencies can
be achieved (taking into account the derating factors):
Table 9-5 Maximum output frequency achieved by increasing the pulse frequency
Pulse frequency
[kHz]
Maximum output frequency
[Hz]
1,25 100
2 160
2,5 200
4 300
1)
5 300
1)
1)
The maximum output frequency is limited to 300 Hz due to the closed-loop control.
9.3.8.2 Parameters
p0009
Device commissioning parameter filter
p0112
Sampling times pre-setting p0115
p0113
Selects the minimum pulse frequency
p0115
Sampling times
p1800
Pulse frequency
p4099
TM31 inputs/outputs, sampling time