8.3 Digital outputs
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
299
Example: changing analog output 0 from current to voltage output –10 V ... +10 V and setting the
characteristic
Voltage output present at terminal 1, ground is at terminal 2
Set TM31.AO_type [analog output 0] to -10 V ... +10 V.
Set TM31.AO_char. x1 to 0.00 %.
Set TM31.AO_char. y1 to 0.000 V.
Set TM31.AO_char. x2 to 100.00%.
Set TM31.AO_char. y2 to 10.000 V.
8.3 Digital outputs
Description
Four bi-directional digital outputs (terminal X541) and two relay outputs (terminal X542) are
available. These outputs are, for the most part, freely parameterizable.
Signal flow diagram
,QYHUVLRQ
 5HDG\WRVWDUW
 2SHUDWLRQHQDEOHG
 5DPSXSUDPSGRZQ
FRPSOHWHG
 5HDG\WRRSHUDWH
U
U
U
U

S
S
S
S
S
S
'2
'2
;
','2
','2
','2

','2






;
0
S

S

S









Figure 8-2 Signal flow diagram: Digital outputs