Appendix
A.2 Parameter macros
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
501
A.2 Parameter macros
Parameter macro p0015 = S150 cabinet unit
This macro is used to make default settings for operating the cabinet unit.
Table A-1 Parameter macro p0015 = S150 cabinet unit
Sink Source
Parameter Description DO Parameter Description DO
p0500 Technology application Vector 0 Standard drive Vector
p0600 Motor temperature sensor for
monitoring
Vector 0 No sensor Vector
p0601 Motor temperature sensor type Vector 0 No sensor Vector
p0603[0] CI: Motor temperature Vector r4105 Sensor on TM31 TM31
p0603[1] CI: Motor temperature Vector
p0604 Motor overtemperature alarm threshold Vector 120 (Factory setting) Vector
p0605 Motor overtemperature fault threshold Vector 155 (Factory setting) Vector
p0606 Motor overtemperature timer Vector 0 (Factory setting) Vector
p0610 Response to motor overtemperature
condition
Vector 1 Display fault, for alarm Imax red. Vector
p0700[0] Macro binector input (BI) Vector 70006 TM31 terminals Vector
p0857 Power module monitoring time Vector 30000 30 seconds Vector
p0864 BI: Infeed operation Vector r0863.0 A_Inf
p1000[0] Macro connector inputs (CI) for speed
setpoints
Vector 10002 TM31_AI0 Vector
p1001 CO: Fixed speed setpoint 1 Vector 300 rpm Vector
p1002 CO: Fixed speed setpoint 2 Vector 600 rpm Vector
p1003 CO: Fixed speed setpoint 3 Vector 1500 rpm Vector
p1083 CO: Speed limit in positive direction of
rotation
Vector 6000 rpm Vector
p1086 CO: Speed limit in negative direction
of rotation
Vector -6000 rpm Vector
p1115 Ramp-function generator selection Vector 1 Extended RFG Vector
p1120 Ramp-function generator ramp-up time Vector 20 s Vector
p1121 Ramp-function generator ramp-down
time
Vector 30 s Vector
p1135 OFF3 ramp-down time Vector 10 s Vector
p1200 FlyRest oper mode Vector 0 Flying restart not active Vector
p1208.0 BI: WEA infeed fault Vector r2139.3 Fault active A_INF
p1208.1 BI: WEA infeed supply break Vector r0863.2 Drive link - infeed supply break A_INF
p1240 Vdc controller configuration Vector 0 Disable Vdc-max controller Vector
p1280 Vdc controller configuration (U/f) Vector 0 Disable Vdc-max controller Vector
p1300 Open-loop/closed-loop control
operating mode
Vector 20 Sensorless speed control Vector
p1911 Number of phases to be identified Vector 3 3 phases Vector
p2051[0] CI: PROFIBUS PZD send word Vector r2089[0] STW1 Vector
p2051[1] CI: PROFIBUS PZD send word Vector r0063 n-act Vector
p2051[2] CI: PROFIBUS PZD send word Vector r0068 I-act Vector
p2051[3] CI: PROFIBUS PZD send word Vector r0080 M-act Vector