Appendix
A.2 Parameter macros
Drive converter cabinet units
502 Operating Instructions, 07/07, A5E00288214A
Sink Source
Parameter Description DO Parameter Description DO
p2051[4] CI: PROFIBUS PZD send word Vector r0082 P-act Vector
p2051[5] CI: PROFIBUS PZD send word Vector r2131 FAULT Vector
p2080[0] BI: PROFIBUS send status word 1 Vector r0899[0] Ready to power up Vector
p2080[1] BI: PROFIBUS send status word 1 Vector r0899[1] Ready Vector
p2080[2] BI: PROFIBUS send status word 1 Vector r0899[2] Operation enabled Vector
p2080[3] BI: PROFIBUS send status word 1 Vector r2139[3] Fault Vector
p2080[4] BI: PROFIBUS send status word 1 Vector r0899[4] No OFF2 Vector
p2080[5] BI: PROFIBUS send status word 1 Vector r0899[5] No OFF3 Vector
p2080[6] BI: PROFIBUS send status word 1 Vector r0899[6] Power-on inhibit Vector
p2080[7] BI: PROFIBUS send status word 1 Vector r2139[7] Alarm present Vector
p2080[8] BI: PROFIBUS send status word 1 Vector r2197[7] Setpoint/actual value deviation in
tolerance
Vector
p2080[9] BI: PROFIBUS send status word 1 Vector r0899[9] Control from PLC Vector
p2080[10] BI: PROFIBUS send status word 1 Vector r2199[1] Comparison value reached Vector
p2080[11] BI: PROFIBUS send status word 1 Vector r1407[7] M/I/P limiting not active Vector
p2080[12] BI: PROFIBUS send status word 1 Vector 0 Vector
p2080[13] BI: PROFIBUS send status word 1 Vector r2129[14] No alarm for motor overtemperature Vector
p2080[14] BI: PROFIBUS send status word 1 Vector r2197[3] Clockwise Vector
p2080[15] BI: PROFIBUS send status word 1 Vector r2129[15] No alarm for therm. overload of power
unit
Vector
p2088 PROFIBUS Invert status word Vector B800h Vector
p2128[14] Select fault/alarm code for trigger Vector 7910 Alarm, motor overtemperature Vector
p2128[15] Select fault/alarm code for trigger Vector 5000 Alarm for therm. overload of power
unit
Vector
p2153 Speed actual value filter time constant Vector 20 ms Vector
p0840[0] ON/OFF 1 A_INF r0863.1 Energize line contactor Vector
p2105 BI: 3. Acknowledge faults A_INF r1214.3 Automatic restart status – set
acknowledgement command
Vector
p1207 BI: WEA link, following DO A_INF r1214.2 Automatic restart status – restart
active
Vector
p4053[0] TM31 analog inputs, smoothing time
constant
TM31 0 ms TM31
p4053[1] TM31 analog inputs, smoothing time
constant
TM31 TM31
p4056[0] TM31 analog inputs, type TM31 2 Current 0...20 mA TM31
p4056[1] TM31 analog inputs, type TM31 2 Current 0...20 mA TM31
p4076[0] TM31 analog outputs, type TM31 0 Current 0...20 mA TM31
p4076[1] TM31 analog outputs, type TM31 0 Current 0...20 mA TM31
p4071[0] Signal analog output 0 TM31 r0063 Actual speed smoothed TM31
p4071[1] Signal analog output 1 TM31 r0068 Absolute current actual value TM31
p4100 TM31 temperature evaluation, sensor
type
TM31 0 (Factory setting) TM31
p4102[0] TM31 temperature evaluation
fault/alarm threshold
TM31 251°C Message being generated TM31
p4102[1] TM31 temperature evaluation
fault/alarm threshold
TM31 251°C Message being generated TM31