Operation
6.4 Command sources
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
187
6.4 Command sources
6.4.1 "Profidrive" default setting
Requirements
The "PROFIdrive" default setting was chosen during commissioning:
STARTER:
"PROFIdrive"
AOP30:
"5: PROFIdrive"
Command sources
U0DVWHUFRQWURODFWLYH
5(027(352),%86
/2&$/2SHUDWRUSDQHO
/2&$/5(027(NH\
,QWHUQDOFRQWURO
&DELQHWRSHUDWRUSDQHO
352),%86
,QSXWWHUPLQDOV$70
Figure 6-9 Command sources - AOP30 ←→ PROFIdrive
Priority
The command source priorities are shown in the diagram "Command sources - AOP30 ←→
PROFIdrive".
Note
The EMERGENCY STOP and motor protection signals are always active (regardless of the
command source).
All of the supplementary setpoints are deactivated for LOCAL master control.