Operation   
6.8 PROFINET IO 
  Drive converter cabinet units 
252  Operating Instructions, 07/07, A5E00288214A 
6.8.4.2  PROFINET IO with RT 
PROFINET IO with RT is the optimal solution for the integration of I/O systems without 
particular requirements in terms of performance and isochronous mode. This is a solution 
that also uses standard Ethernet in the devices and commercially available industrial 
switches as infrastructure components. A special hardware support is not required.  
Not isochronous 
Because standard Ethernet does not support any synchronization mechanisms, isochronous 
operation is not possible with PROFINET IO with RT! 
The realtime capability is comparable with the present PROFIBUS DP solutions with 12 
MBaud, whereby a sufficiently large bandwidth portion is available for the parallel 
transmission of IT services on the same line. 
PROFINET IO telegrams have priority over IT telegrams in accordance with IEEE802.1q. 
This ensures the required determinism in the automation technology. 
Data exchange 
Communication is possibly only within a network (subnet). 
Refresh time 
The refresh time is in the range 1 ms, 2 ms and 4 ms. The real refresh time depends on the 
bus load, the devices used and the quality structure of the I/O data. The refresh time is a 
multiple of the send clock. 
6.8.4.3  Configuring RT communication on Simatic 
RT communications with GSDML v1.0 
Requirement 
For example, a Simatic 300 CPU version <2.5 is configured with a PROFINET sub-network, 
and a drive is inserted via the GSD file SINAMICS S120 CBE20 Pilot RT.  
Now, drives and drive objects (DOs) are to be parameterized. For this version of the drive, 
the telegrams must be inserted step-by-step. To start, a Parameter Access Point must be 
inserted, then a telegram and then again another Parameter Access Point - and so on. 
 
 
Note 
The sequence in which the telegram is created must be the same as the sequence of the 
drive objects in the configuration screen for the drive in STARTER.