Operation
6.6 PROFIBUS
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
211
6.6.6 Description of status words and actual values
Overview
Table 6-14 Overview of status words and actual values
Abbreviation Description Parameters Function diagram
ZSW 1 Status word 1 (interface mode SINAMICS /
MICROMASTER, p2038 = 0)"
See table "Status word 1 (interface
mode SINAMICS /
MICROMASTER, p2038 = 0)"
FP2452
ZSW 1 Status word 1 (interface mode PROFIdrive
VIK-NAMUR, p2038 = 2)
See table "Status word 1 (interface
mode PROFIdrive VIK-NAMUR,
p2038 = 2)"
FP2451
N_act_A Speed setpoint A (16 bit) r0063[0] FP4715
N_act_B Speed setpoint B (32 bit) r0063 FP4710
Ia_act Actual value of current r0068[0] FP6714
M_act Actual torque value r0080[0] FP6714
P_act Actual power value r0082[0] FP6714
N_act_SMOOTH Actual speed smoothed r0063[1] FP4715
Ia_act_SMOOTH Current actual value, smoothed r0068[1] FP6714
M_act_SMOOTH Torque actual value, smoothed r0080[1] FP6714
P_act_SMOOTH Power actual value, smoothed r0082[1] FP6714
MELD_NAMUR VIK-NAMUR message bit bar r3113, see table "NAMUR
message bit bar"
--
WARN_CODE Alarm code r2132 FP8065
ERROR_CODE Error code r2131 FP8060
Status word 1 (interface mode SINAMICS / MICROMASTER, p2038 = 0)"
Table 6-15 Status word 1 (interface mode SINAMICS / MICROMASTER, p2038 = 0)"
Bit Meaning Explanation BICO
1 Ready to power up
Power supply on, electronics initialized, line contactor
released if necessary, pulses inhibited.
0 Ready to power up
0 Not ready to power up
BO: r0899.0
1 Ready
Voltage at Line Module (i.e. line contactor closed (if used)),
field being built up.
1 Ready
0 Not ready
Cause: No ON command has been issued.
BO: r0899.1
1 Operation enabled
Enable electronics and pulses, then ramp up to active
setpoint.
2 Operation enabled
0 Operation inhibited
BO: r0899.2