Maintenance and servicing 
11
11.1  Chapter content 
This chapter provides information on the following:  
●  Maintenance and servicing procedures that have to be carried out on a regular basis to 
ensure the availability of the cabinet units. 
●  Exchanging device components when the unit is serviced 
●  Forming the DC link capacitors 
●  Upgrading the cabinet unit firmware 
●  Loading the new operator panel firmware from the PC. 
 
DANGER 
 
 
Before carrying out any maintenance or repair work on the de-energized cabinet unit, 
wait for 5 minutes after switching off the supply voltage. This allows the capacitors to 
discharge to a harmless level (< 25 V) after the supply voltage has been switched off. 
Before starting work, you should also measure the voltage after the 5 minutes have 
elapsed. The voltage can be measured on DC link terminals DCP and DCN. 
DANGER 
 
 
When the external power supply for individual options (L50 / L55) or the external 230 V 
AC auxiliary supply is connected, dangerous voltages are still present in the cabinet unit 
even when the main circuit breaker is open.