EasyManua.ls Logo

Siemens SINAMICS S150 - Motor Changeover;Selection; Description; Example of Changing over between Two Motors

Siemens SINAMICS S150
520 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions, monitoring, and protective functions
9.3 Drive functions
Drive converter cabinet units
324 Operating Instructions, 07/07, A5E00288214A
9.3.6 Motor changeover/selection
9.3.6.1 Description
The motor data set changeover is, for example, used for:
Changing over between different motors
Motor data adaptation
Note
To switch to a rotating motor, the "flying restart" function must be activated.
9.3.6.2 Example of changing over between two motors
Prerequisites
The drive has been commissioned for the first time.
2 motor data sets (MDS), p0130 = 2
2 drive data sets (DDS), p0180 = 2
2 digital outputs to control the auxiliary contactors
2 digital inputs to monitor the auxiliary contactors
1 digital input to select the data set
2 auxiliary contactors with auxiliary contacts (1 NO contact)
2 motor contactors with positively-driven auxiliary contacts (1 NC contact, 1NO contact)
~
M
3
K 1
K 1 H
K 2
K 2
K 2 H
K 1
~
M
3
K 1 H
K 2 H
K 1
K 2
S 1
U
U
S
S>@
S>@
U
Figure 9-6 Example of motor changeover