Appendix
A.2 Parameter macros
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
503
Parameter macro p0700 = 5: PROFIdrive (70005)
This macro is used to set the PROFIdrive interface as the default command source.
Table A-2 Parameter macro p0700 = 5: PROFIdrive
Sink Source
Parameters Description DO Parameters Description DO
p0840[0] ON/OFF1 Vector r2090.0 PZD 1 bit 0 Vector
p0844[0] No OFF2_1 Vector r2090.1 PZD 1 bit 1 Vector
p0845[0] No OFF2_2 Vector r0722.3 CU DI3 CU
p0848[0] No OFF3_1 Vector r2090.2 PZD 1 bit 2 Vector
p0849[0] No OFF3_2 Vector r0722.2 CU DI2 CU
p0806 Inhibit LOCAL mode Vector 0
p0810 Switchover CDS bit 0 Vector 0
p0852 Enable operation Vector r2090.3 PZD 1 bit 3 Vector
p0854 Control from the PLC Vector r2090.10 PZD 1 bit 10 Vector
p0922 PROFIdrive PZD telegram selection Vector 999 Free telegram configuration
p1020 FSW bit 0 Vector 0
p1021 FSW bit 1 Vector 0
p1035 MOP higher Vector r2090.13 PZD 1 bit 13 Vector
p1036 MOP lower Vector r2090.14 PZD 1 bit 14 Vector
p1055 Jog bit 0 Vector 0
p1056 Jog bit 1 Vector 0
p1113 Direction of rotation changeover Vector r2090.11 PZD 1 bit 11 Vector
p1140 Enable RFG Vector r2090.4 PZD 1 bit 4 Vector
p1141 Start RFG Vector r2090.5 PZD 1 bit 5 Vector
p1142 Enable nsetp Vector r2090.6 PZD 1 bit 6 Vector
p2103 1. Acknowledge fault Vector r2090.7 PZD 1 bit 7 Vector
p2104 1. Acknowledge fault Vector r4022.3 TM31 DI3 TM31
p2106 Ext. fault_1 Vector r0722.1 CU DI1 CU
p2107 Ext. fault_2 Vector 1
p2112 Ext. alarm_1 Vector r0722.0 CU DI0 CU
p2116 Ext. alarm_2 Vector 1
p0738 DI/DO8 CU 1 +24 V CU
p0748[8] Invert DI/DO8 CU 0 Not inverted
p0728[8] Set DI/DO8 input or output CU 1 Output CU
p0739 DI/DO9 CU 1 +24 V CU
p0748[9] Invert DI/DO9 CU 0 Not inverted
p0728[9] Set DI/DO9 input or output CU 1 Output CU
p0740 DI/DO10 CU 1 +24 V CU
p0748[10] Invert DI/DO10 CU 0 Not inverted
p0728[10] Set DI/DO10 input or output CU 1 Output CU
p0741 DI/DO11 CU 1 +24 V CU
p0748[11] Invert DI/DO11 CU 0 Not inverted