Appendix
A.2 Parameter macros
Drive converter cabinet units
504 Operating Instructions, 07/07, A5E00288214A
Sink Source
Parameters Description DO Parameters Description DO
p0728[11] Set DI/DO11 input or output CU 1 Output CU
p0742 DI/DO12 CU 1 +24 V CU
p0748[12] Invert DI/DO12 CU 0 Not inverted
p0728[12] Set DI/DO12 input or output CU 1 Output CU
p0743 DI/DO13 CU r0899.6 Switching on inhibited Vector
p0748[13] Invert DI/DO13 CU 1 Inverted
p0728[13] Set DI/DO13 input or output CU 1 Output CU
p0744 DI/DO14 CU 1 +24 V CU
p0748[14] Invert DI/DO14 CU 0 Not inverted
p0728[14] Set DI/DO14 input or output CU 1 Output CU
p0745 DI/DO15 CU r2138.7 Ack. fault Vector
p0748[15] Invert DI/DO15 CU 0 Not inverted
p0728[15] Set DI/DO15 input or output CU 1 Output CU
p2103 1. Acknowledge fault TM31 r2090.7 PZD 1 bit 7 Vector
p2104 Acknowledge fault 2 TM31 r4022.3 TM31 DI3 TM31
p4030 DO0 TM31 r0899.11 Pulses enabled Vector
p4031 DO1 TM31 r2139.3 Fault Vector
p4038 DO8 TM31 r0899.0 Ready to start Vector
p4028.8 Set DI/DO8 input or output TM31 1 Output TM31
p4039 DO9 TM31 0
p4028.9 Set DI/DO9 input or output TM31 0
p4040 DO10 TM31 0
p4028.10 Set DI/DO10 input or output TM31 0
p4041 DO11 TM31 0
p4028.11 Set DI/DO11 input or output TM31 0
p2103 1. Acknowledge fault A_INF r2090.7 PZD 1 bit 7 Vector
p2104 Acknowledge fault 2 A_INF r4022.3 TM31 DI3 TM31