Output terminals
8.3 Digital outputs
Drive converter cabinet units
300 Operating Instructions, 07/07, A5E00288214A
Factory settings
Table 8-5 Factory settings for digital outputs
digital output Terminal Factory setting
DO0 X542: 2,3 "Enable pulses"
DO1 X542: 5,6 "No fault"
DI/DO8 X541: 2 "Ready to start"
DI/DO9 X541: 3
DI/DO10 X541:4
DI/DO11 X541: 5
Selection of possible connections for the digital outputs
Table 8-6 Selection of possible connections for the digital outputs
Signal Bit in status
word 1
Parameters
1 = Ready to start 0 r0889.0
1 = Ready to operate (DC link loaded, pulses blocked) 1 r0889.1
1 = Operation enabled (drive follows n_setp) 2 r0889.2
1 = Fault present 3 r2139.3
0 = Coast to stop active (OFF2) 4 r0889.4
0 = Fast stop active (OFF3) 5 r0889.5
1 = Power-on disable 6 r0889.6
1 = Alarm present 7 r2139.7
1 = Speed setpoint/actual deviation in the tolerance bandwidth (p2163, p2166) 8 r2197.7
1 = Control required to PLC 9 r0899.9
1 = f or n comparison value reached or exceeded (p2141, p2142) 10 r2199.1
1 = I, M, or P limit reached (p0640, p1520, p1521) 11 r1407.7
Reserved 12
0 = Alarm motor overtemperature (A7910) 13 r2129.14
Reserved 14
0 = Alarm thermal overload in power unit (A5000) 15 r2129.15
1 = Pulses enabled (inverter is clocking, drive is carrying current) r0899.11
1 = n_act ≤ p2155 r2197.1
1 = n_act > p2155 r2197.2
1 = Ramp-up/ramp-down completed r2199.5
1 = n_act < p2161 (preferably as n_min or n=0 message) r2199.0
1 = Torque setpoint < p2174 r2198.10
1 = LOCAL mode active (control via operator panel) r0807.0
0 = Motor blocked r2198.6