Output terminals
8.2 Analog outputs
Drive converter cabinet units
298 Operating Instructions, 07/07, A5E00288214A
Signals for the analog outputs: object A_INF
Table 8-3 List of signals for the analog outputs - object A_INF
Signal Parameter Unit Scaling (100 %=...)
See table below
Output current r0068 Aeff p2002
DC link voltage r0070 V p2001
Modulation depth r0074 % Reference modulation depth
Torque-generating current setpoint r0077 A p2002
Torque-generating actual current r0078 A p2002
Output power r0082 kW r2004
Scalings for object A_INF
Table 8-4 Scalings for object A_INF
Variable Scaling parameter Default for quick commissioning
Reference frequency 100 % = p2000 p2000 = p0211
Reference voltage 100 % = p2001 p2001 = r0206/r0207
Reference current 100 % = p2002 p2002 = r0207
Reference power 100 % = r2004 r2004 = r0206
Reference modulation depth 100 % = Maximum output voltage without
overload
Reference temperature 100% = 100°C
Example: changing analog output 0 from current to voltage output –10 V ... +10 V
Voltage output present at terminal 1, ground is at terminal 2
Set analog output type 0 to -10 ... +10 V.