Commissioning
5.8 Parameter reset to factory settings
Drive converter cabinet units
170 Operating Instructions, 07/07, A5E00288214A
Parameter reset via STARTER
With STARTER, the parameters are reset in online mode. The required steps are described
below:
Step Selection in toolbar
Choose
Project > Connect to target system
Click the drive unit whose parameters you want to reset to the factory settings
and click Restore factory settings icon in the toolbar.
To confirm, click OK.
Choose
Target system > Copy from RAM to ROM
Note
The Copy from RAM to ROM icon is only active when the drive unit is selected in the project
navigator.
When the parameters have been reset to the factory settings, initial commissioning needs to
be carried out.