Operation
6.5 Setpoint sources
Drive converter cabinet units
196 Operating Instructions, 07/07, A5E00288214A
p4059
Analog inputs, characteristic value x2
p4060
Analog inputs, characteristic value y2
p4063
Analog inputs offset
Note
In the factory setting and after basic commissioning, an input current of 20 mA is equal to the
main setpoint 100 % reference speed (p2000), which has been set to the maximum speed
(p1082).
Example: Changing Analog Input 0 from Current to Voltage Input –10 to +10 V
Table 6-5 Example: setting analog input 0
Current / voltage switchover
Set current/voltage selector to "Voltage" ("V").
Set analog input type 0 to -10 V... +10 V.
Note
The new analog input must then be stored on the CompactFlash card so that it is protected
in the event of a power failure.
F3505 – Fault: "Analog input, wire breakage"
The fault is triggered when analog input type (p4056) is set to 3 (4 ... 20 mA with open-circuit
monitoring) and the input current of 2 mA has been undershot.
The fault value can be used to determine the analog input in question.
Table 6-6 Fault screen
Component number
4: module -A60
5: module -A61 (optional)

) ) ) ) )
[KH[)YDOXH
&DXVH
70:LUHEUHDNDQDORJLQSXW
5HPHG\
70&KHFNDQDORJLQSXWFDEOHV
70$QDORJLQSXWZLUHEUHDN
%DFN
0: Analog input 0: -X521:1/2
1: Analog input 1: -X521:3/4