Device overview   
2.5 Type plate 
  Drive converter cabinet units 
26  Operating Instructions, 07/07, A5E00288214A 
Type plate data (from type plate above)  
Table 2-2  Data on the type plate 
Specification  Value  Explanation 
Input 
 
3 AC 
380 – 480 V 
239 A 
Three-phase connection 
Rated input voltage 
Rated input current 
Output 
 
3 AC 
0 – 480 V 
210 A 
Three-phase connection 
Rated output voltage 
Rated output current 
Temperature range 
 
0 – 40 °C  Ambient temperature range within which the cabinet unit can operate under 100 
% load 
Degree of protection 
 
IP20  Degree of protection 
Duty class 
 
I  I: Duty class I to EN 60146-1-1 = 100 % (continuously) 
(with the specified current values, the cabinet unit can operate continuously 
under 100 % load) 
Cooling method 
 
AF  A: Cooling medium: air 
F: circulation method: forced cooling, drive unit (fan) in the device 
Weight 
 
  Weight of the cabinet unit 
 
Explanation of the option short codes 
Table 2-3  Explanation of the option short codes 
Input options 
L26  Main circuit breaker incl. fuses for output currents < 800 A 
Output options 
L08  Motor reactor 
L10  dV/dt filter with Voltage Peak Limiter 
L15  Sinusoidal filter (only for the voltage range 380 V - 480 V 3 AC to 200 kW) 
Input and output options 
M70  EMC shield bus (cable connection from below) 
Motor protection and safety functions 
L45  EMERGENCY STOP pushbutton in cabinet door 
L57  EMERGENCY STOP category 0 (230 V AC or 24 V DC, uncontrolled stop) 
L59   EMERGENCY STOP category 1, 230 V AC, controlled stop 
L60  EMERGENCY STOP category 1 (24 V DC, controlled stop) 
L83  Thermistor motor protection unit with PTB approval (alarm) 
L84  Thermistor motor protection unit with PTB approval (shutdown) 
L86  PT100 evaluation unit (for 6 PT100 sensors) 
L87  Insulation monitoring 
M60  Additional shock-hazard protection