Setpoint channel and closed-loop control 
  7.2 Setpoint channel 
Drive converter cabinet units 
Operating Instructions, 07/07, A5E00288214A 
265 
Parameters 
 
•  r1119 
Ramp-function generator setpoint at the input 
•  p1120 
Ramp-function generator ramp-up time 
•  p1121 
Ramp-function generator ramp-down time 
•  p1130 
Ramp-function generator initial rounding time 
•  p1131 
Ramp-function generator final rounding time 
•  p1134 
Ramp-function generator rounding type 
•  p1135 
OFF3 ramp-down time 
•  p1136 
OFF3 initial rounding time 
•  p1137 
OFF3 final rounding time 
•  r1150 
Ramp-function generator speed setpoint at the output 
•  p1151 
Ramp-function generator configuration 
 
 
 
Note 
The effective ramp-up time increases when you enter initial and final rounding times. 
Effective ramp-up time = p1120 + (0.5 x p1130) + (0.5 x p1131)