Functions, monitoring, and protective functions   
9.3 Drive functions 
  Drive converter cabinet units 
320  Operating Instructions, 07/07, A5E00288214A 
The startup attempt has been completed successfully once the flying restart and 
magnetization of the motor (induction motor) has been completed (r0056.4 = 1) and one 
additional second has expired. The startup counter is not reset to the initial value p1211 until 
this point.  
If additional faults occur between successful acknowledgement and the end of the startup 
attempt, then the startup counter, when it is acknowledged, is also decremented. 
Monitoring time power restoration (p1213) 
The monitoring time starts when the faults are detected. If the automatic acknowledgements 
are not successful, the monitoring time will continue. If the drive has not successfully 
restarted by the time the monitoring time expires (flying restart and motor magnetization 
must have been completed: r0056.4 = 1), fault F07320 is output. Monitoring is deactivated 
by setting p1213 = 0.  
If p1213 is set to a value lower than the sum of p1212, the magnetization time r0346 and the 
additional delay time due to flying restart, then fault F07320 will be generated on every 
restart attempt. If, for p1210 = 1, the time in p1213 is set to a value lower than p1212, then 
fault F07320 will also be generated on every restart attempt. The monitoring time must be 
extended if the faults that occur cannot be immediately and successfully acknowledged (e.g., 
when faults are permanently present). 
Parameters 
 
•  p1210 
Automatic restart mode 
•  p1211 
Automatic restart, start attempts 
•  p1212 
Automatic restart, delay time start attempts 
•  p1213 
Automatic restart, monitoring line supply return 
Settings 
To prevent the motor from switching to phase opposition when the drive is being restarted, 
there is a delay while the motor demagnetizes (t = 2.3 x motor magnetization time constant). 
Once this time has elapsed, the inverter is enabled and the motor is supplied with power.