Functions, monitoring, and protective functions 
  9.4 Extended functions 
Drive converter cabinet units 
Operating Instructions, 07/07, A5E00288214A 
339 
The output can be scaled via parameter p2295 and the control direction reversed. It can be 
limited via parameters p2291 and p2292 and interconnected as required via a connector 
output (r2294). 
The actual value can be integrated, for example, via an analog input on the TM31. 
If a PID controller has to be used for control reasons, the D component is switched to the 
setpoint/actual value difference (p2263 = 1) unlike in the factory setting. This is always 
necessary when the D component is to be effective, even if the reference variable changes. 
The D component can only be activated when p2274 > 0. 
 
 
Note 
With the entry "0" sec. as power up time or ramp-down time for the ramp function generator 
of the technology controller, the current values of the respective ramp function generator will 
be frozen. 
 
Commissioning 
The "technology controller" function module can be activated by running the commissioning 
Wizard. Parameter r0108.16 indicates whether the function module has been activated. 
Function diagram 
 
FD 7950  Technology controller – fixed values 
FD 7954  Technology controller – motorized potentiometer 
FD 7958  Technology controller – closed-loop controller