Diagnosis / faults and alarms
10.2 Diagnosis
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
413
VSM - Interface Module in the Active Interface Module (-A2)
Table 10-5 Description of the LEDs on the Voltage Sensing Module
LEDs Color Status Description
--- OFF The electronics power supply is missing or lies outside the permissible
tolerance range.
Green Continuous The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Orange Continuous DRIVE-CLiQ communication is being established.
Red Continuous At least one fault is pending on this component.
Note:
LED is driven irrespective of the corresponding messages being
reconfigured.
0.5 Hz flashing
light
Firmware is being downloaded. Green/red
2 Hz flashing
light
Firmware download is complete. Wait for POWER ON.
RDY
Green/orange
or
red/orange
2 Hz flashing
light
Detection of the components via LED is activated (p0144).
Note:
Both options depend on the LED status when module recognition is
activated via p0144 = 1.
SMC10 – encoder evaluation (-A83)
Table 10-6 Description of the LEDs on the SMC10
LEDs Color Status Description
--- OFF The electronics power supply is missing or lies outside the permissible
tolerance range.
Green Continuous The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Orange Continuous DRIVE-CLiQ communication is being established.
Red Continuous At least one fault is pending on this component.
Note:
LED is driven irrespective of the corresponding messages being
reconfigured.
0.5 Hz flashing
light
Firmware is being downloaded. Green/red
2 Hz flashing
light
Firmware download is complete. Wait for POWER ON.
RDY
Green/orange
or
red/orange
2 Hz flashing
light
Detection of the components via LED is activated (p0144).
Note:
Both options depend on the LED status when module recognition is
activated via p0144 = 1.