Technical specifications
12.3 Technical specifications
Drive converter cabinet units
484 Operating Instructions, 07/07, A5E00288214A
Table 12-10 Version A, 380 V – 480 V 3 AC, part 2
Category Unit
Order No. 6SL3710- 7LE33-8AA0 7LE35-0AA0 7LE36-1AA0
Rated motor output
at 400 V, 50 Hz
at 460 V, 60 Hz
kW
hp
200
300
250
400
315
500
Rated input voltage V 380 V to 480 V 3 AC ± 10% (-15% < 1 min)
Rated input current
1)
A 349 447 549
Rated output current A 380 490 605
Base-load current I
L
2)
A 370 477 590
Base-load current I
H
3)
A 340 438 460
Max. output frequency
4)
Hz 160 160 100
Power loss kW 9.3 11.7 15.9
Cooling air requirement m³/s 1.19 1.19 1.96
Sound pressure level at 50/60 Hz dB(A) 72/74 72/74 77/79
Line connection
Recommended: DIN VDE
5)
Maximum: DIN VDE
AWG/MCM
Fixing screw
mm
2
mm
2
2 x 120
4 x 240
4 x (500)
M12 (2 holes)
2 x 185
4 x 240
4 x (500)
M12 (2 holes)
2 x 240
4 x 240
4 x (500)
M12 (2 holes)
Motor connection
Recommended: DIN VDE
5)
Maximum: DIN VDE
AWG/MCM
Fixing screw
mm
2
mm
2
2 x 120
2 x 150
2 x (300)
M12 (2 holes)
2 x 185
2 x 240
2 x (500)
M12 (2 holes)
2 x 240
4 x 240
4 x (500)
M12 (2 holes)
Protective conductor connection
Fixing screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Approx. weight (standard version) kg 980 980 1716
Frame sizes
Active Interface Module
Active Line Module
Motor Module
GI
GX
GX
GI
GX
GX
HI
HX
HX
Dimensions (standard version)
Width x height x depth
mm
1800 x 2,000 x 600
1800 x 2,000 x 600
2200 x 2,000 x 600
Recommended protection
Line protection
(with option L26)
Rated current
Frame size to DIN 43620-1
Line and semi-cond. protection
(without option L26)
Rated current
Frame size to DIN 43620-1
A
A
3NA3365
500
3
3NE1334-2
500
2
3NA3372
630
3
3NE1436-2
630
3
3NA3475
800
4
3NE1438-2
800
3
1)
The currents are based on a power factor of cos ϕ = 1 and include 10 A for the external auxiliary equipment (as used, for
example, with options L19 or B03).
2)
The base-load current (I
L
) is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
3)
The base-load current (I
H
) is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
4)
Maximum output frequency at factory-set default pulse frequency (for information on increasing the output frequency,
see "Functions, monitoring and protective functions/Increasing the output frequency"; for information on derating data, see
"Derating data").
5)
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC
(National Electrical Code) or CEC (Canadian Electrical Code) standards.