Technical specifications   
12.3 Technical specifications 
  Drive converter cabinet units 
492  Operating Instructions, 07/07, A5E00288214A 
Table 12-18  Version A, 660 V – 690 V 3 AC, part 6 
Category  Unit       
Order No. 6SL3710- 7LH41-3AA0   
Rated motor output  kW  1200     
Rated input voltage  V  660 V to 690 V 3 AC ± 10% (-15% < 1 min) 
Rated input current 
1)
  A  1142     
Rated output current  A  1270     
Base-load current I
L
2)
  A  1230     
Base-load current I
H
3)
  A  1136     
Max. output frequency 
4)
  Hz  100     
Power loss  kW  40.1     
Cooling air requirement  m³/s  2.6     
Sound pressure level at 50/60 Hz  dB(A)  77/79     
Line connection 
Recommended: DIN VDE 
5)
 
Maximum: DIN VDE 
AWG/MCM 
Fixing screw 
 
mm
2
 
mm
2
 
 
 
4 x 240 
8 x 240 
8 x (500) 
M12 (4 holes) 
 
Motor connection 
Recommended: DIN VDE 
5)
 
Maximum: DIN VDE 
AWG/MCM 
Fixing screw 
 
mm
2
 
mm
2
 
 
 
4 x 240 
6 x 240 
6 x (500) 
M12 (3 holes) 
 
Protective conductor connection 
Fixing screw 
 
M12 (18 holes) 
 
Approx. weight (standard version)  kg  2408     
Frame sizes 
Active Interface Module 
Active Line Module 
Motor Module 
 
JI 
JX 
JX 
 
Dimensions (standard version)  
Width x height x depth 
 
mm 
 
2800 x 2,000 x 600 
 
Recommended protection 
Line protection 
(with option L26) 
Rated current 
Frame size to DIN 43620-1 
Line and semi-cond. protection 
(without option L26) 
Rated current 
Frame size to DIN 43620-1 
 
 
 
A 
 
 
 
A 
 
 
 
Circuit breaker 
 
 
 
Circuit breaker 
 
 
 
1)
 The currents are based on a power factor of cos ϕ = 1 and include 10 A for the external auxiliary equipment (as used, for 
example, with options L19 or B03). 
2)
 The base-load current (I
L
) is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s 
(see "Overload capability"). 
3)
 The base-load current (I
H
) is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s 
(see "Overload capability"). 
4)
 Maximum output frequency at factory-set default pulse frequency (for information on increasing the output frequency, 
see "Functions, monitoring and protective functions/Increasing the output frequency"; for information on derating data, see 
"Derating data"). 
5)
 The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC 
(National Electrical Code) or CEC (Canadian Electrical Code) standards.