Technical specifications
12.3 Technical specifications
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
495
Table 12-21 Version A, 500 V – 690 V 3 AC, part 3
Category Unit
Order No. 6SL3710- 7LG32-6AA0 7LG33-3AA0 7LG34-1AA0
Rated motor output kW 250 315 400
Rated input voltage V 500 V to 690 V 3 AC ± 10% (-15% < 1 min)
Rated input current
1)
A 242 304 375
Rated output current A 260 330 410
Base-load current I
L
2)
A 250 320 400
Base-load current I
H
3)
A 233 280 367
Max. output frequency
4)
Hz 100 100 100
Power loss kW 11.1 12.5 17.7
Cooling air requirement m³/s 1.19 1.19 1.96
Sound pressure level at 50/60 Hz dB(A) 75/77 75/77 77/79
Line connection
Recommended: DIN VDE
5)
Maximum: DIN VDE
AWG/MCM
Fixing screw
mm
2
mm
2
2 x 95
4 x 240
4 x (500)
M12 (2 holes)
2 x 120
4 x 240
4 x (500)
M12 (2 holes)
2 x 185
4 x 240
4 x (500)
M12 (2 holes)
Motor connection
Recommended: DIN VDE
5)
Maximum: DIN VDE
AWG/MCM
Fixing screw
mm
2
mm
2
2 x 95
2 x 185
2 x (350)
M12 (2 holes)
2 x 120
2 x 240
2 x (500)
M12 (2 holes)
2 x 185
4 x 240
4 x (500)
M12 (2 holes)
Protective conductor connection
Fixing screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Approx. weight (standard version) kg 892 892 1716
Frame sizes
Active Interface Module
Active Line Module
Motor Module
GI
GX
GX
GI
GX
GX
HI
HX
HX
Dimensions (standard version)
Width x height x depth
mm
1600 x 2,000 x 600
1600 x 2,000 x 600
2200 x 2,000 x 600
Recommended protection
Line protection
(with option L26)
Rated current
Frame size to DIN 43620-1
Line and semi-cond. protection
(without option L26)
Rated current
Frame size to DIN 43620-1
A
A
3NA3354-6
355
3
3NE1331-2
350
2
3NA3365-6
500
3
3NE1334-2
500
2
3NA3365-6
500
3
3NE1334-2
500
2
1)
The currents are based on a power factor of cos ϕ = 1 and include 10 A for the external auxiliary equipment (as used, for
example, with options L19 or B03).
2)
The base-load current (I
L
) is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
3)
The base-load current (I
H
) is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
4)
Maximum output frequency at factory-set default pulse frequency (for information on increasing the output frequency,
see "Functions, monitoring and protective functions/Increasing the output frequency"; for information on derating data, see
"Derating data").
5)
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC
(National Electrical Code) or CEC (Canadian Electrical Code) standards.