Electrical installation
4.6 Power connections
Drive converter cabinet units
56 Operating Instructions, 07/07, A5E00288214A
Table 4-4 Supply voltage assignments for setting the fan transformer (380 V – 480 V 3AC)
Supply voltage Fan transformer tap (-G1-T10, -U1-T10)
380 V ± 10% 380 V
400 V ± 10% 400 V
440 V ± 10% 440 V
480 V ± 10% 480 V
Table 4-5 Supply voltage assignments for setting the fan transformer (660 V – 690 V 3AC)
Supply voltage Fan transformer tap (-G1-T10, -U1-T10)
660 V ± 10% 660 V
690 V ± 10% 690 V
Table 4-6 Supply voltage assignments for setting the fan transformer (500 V – 600 V 3 AC)
Supply voltage Fan transformer tap (-G1-T10, -U1-T10)
500 V ± 10% 500 V
525 V ± 10% 525 V
575 V ± 10% 575 V
600 V ± 10% 600 V
660 V ± 10% 660 V
690 V ± 10% 690 V