Electrical installation
4.9 Other connections
Drive converter cabinet units
70 Operating Instructions, 07/07, A5E00288214A
Commissioning
In the event of commissioning using the STARTER or AOP30, the sine-wave filter must be
activated by means of appropriate selection screenforms or dialog boxes, see the section
titled "Commissioning".
The following parameters are changed automatically during commissioning.
Table 4-20 Parameter settings for sinusoidal filters with SINAMICS S150
Parameter Name Setting
p0233 Power module motor reactor Filter inductance
p0234 Power module sinusoidal filter
capacitance
Filter capacitance
p0290 Power module overload response Disable pulse frequency reduction
p1082 Maximum speed Fmax filter / pole pair number
p1800 Pulse frequency Nominal pulse frequency of the filter (see
previous table)
p1802 Modulator mode Space-vector modulation without
overmodulation
Note
When the factory settings are restored, parameter p0230 is reset.
The parameter must be reset if the system is commissioned again.